Electrical Q & Ans; A Part-1
1) Why ELCB cannot work if Neutral input of ELCB does not connect to ground?
- ELCB is used to detect earth leakage
fault. Once the phase and neutral are connected in an ELCB, the current
will flow through phase and that same current will have to return
neutral so resultant current is zero.
- Once there is a ground fault in the
load side, current from phase will directly pass through earth and it
will not return through neutral through ELCB. That means once side
current is going and not returning and hence because of this difference
in current ELCB will trip and it will safe guard the other circuits from
faulty loads. If the neutral is not grounded fault current will
definitely high and that full fault current will come back through ELCB,
and there will be no difference in current.
2) What is the difference between MCB & MCCB, Where it can be used?
- MCB is miniature circuit breaker which is thermal operated and use for short circuit protection in small current rating circuit.
- Normally it is used where normal current is less than 100A.
- MCCB moulded case circuit breaker and
is thermal operated for over load current and magnetic operation for
instant trip in short circuit condition. Under voltage and under
frequency may be inbuilt.
- Normally it is used where normal current is more than 100A.
3) Why in a three pin plug the earth pin is thicker and longer than the other pins?
- It depends upon R=ρL/A where area (A)
is inversely proportional to resistance (R), so if area (A) increases, R
decreases & if R is less the leakage current will take low
resistance path so the earth pin should be thicker. It is longer because
the The First to make the connection and last to disconnect should be
earth Pin. This assures Safety for the person who uses the electrical
instrument.
4) Why Delta Star Transformers are used for Lighting Loads?
- For lighting loads, neutral conductor
is must and hence the secondary must be star winding and this lighting
load is always unbalanced in all three phases.
- To minimize the current unbalance in
the primary we use delta winding in the primary So delta / star
transformer is used for lighting loads.
5) What are the advantages of star-delta starter with induction motor?
- The main advantage of using the star
delta starter is reduction of current during the starting of the motor.
Starting current is reduced to 3-4 times of current of Direct online
starting Hence the starting current is reduced , the voltage drops
during the starting of motor in systems are reduced.
6) What is meant by regenerative braking?
- When the supply is cut off for a
running motor, it still continue running due to inertia. In order to
stop it quickly we place a load (resistor) across the armature winding
and the motor should have maintained continuous field supply so that
back e.m.f voltage is made to apply across the resistor and due to load
the motor stops quickly. This type of breaking is called as
“Regenerative Breaking”.
7) When voltage increases
then current also increases then why we need of over voltage relay and
over current relay? Can we measure over voltage and over current by
measuring current only?
- No. We cannot sense the over voltage by
just measuring the current only because the current increases not only
for over voltages but also for under voltage (As most of the loads are
non-linear in nature).So, the over voltage protection & over current
protection are completely different.
- Over voltage relay meant for sensing
over voltages & protect the system from insulation break down and
firing. Over current relay meant for sensing any internal short circuit,
over load condition, earth fault thereby reducing the system failure
& risk of fire. So, for a better protection of the system. It should
have both over voltage & over current relay.
8) If one lamp connects between two phases it will glow or not?
- If the voltage between the two phases is equal to the lamp voltage then the lamp will glow.
- When the voltage difference is big it
will damage the lamp and when the difference is smaller the lamp will
glow depending on the type of lamp.
9) What are HRC fuses and where it is used?
- HRC stand for “high rupturing capacity” fuse and it is used in distribution system for electrical transformers
10) Mention the methods for starting an induction motor?
- The different methods of starting an induction motor
- DOL:direct online starter
- Star delta starter
- Auto transformer starter
- Resistance starter
- Series reactor starter
11) What is the difference between earth resistance and earth electrode resistance?
- Only one of the terminals is evident in
the earth resistance. In order to find the second terminal we should
recourse to its definition:
- Earth Resistance is the resistance
existing between the electrically accessible part of a buried electrode
and another point of the earth, which is far away.
- The resistance of the electrode has the following components:
(A) the resistance of the metal and that of the connection to it.
(B) The contact resistance of the surrounding earth to the electrode.
12) Why most of analog o/p devices having o/p range 4 to 20 mA and not 0 to 20 mA?
- 4-20 mA is a standard range used to
indicate measured values for any process. The reason that 4ma is chosen
instead of 0 mA is for fail safe operation.
- For example: A pressure instrument
gives output 4mA to indicate 0 psi up to 20 mA to indicate 100 psi or
full scale. Due to any problem in instrument (i.e) broken wire, its
output reduces to 0 mA. So if range is 0-20 mA then we can differentiate
whether it is due to broken wire or due to 0 psi.
13) Two bulbs of 100w and 40w respectively connected in series across a 230v supply which bulb will glow bright and why?
- Since two bulbs are in series they will
get equal amount of electrical current but as the supply voltage is
constant across the Bulb (P=V^2/R).So the resistance of 40W bulb is
greater and voltage across 40W is more (V=IR) so 40W bulb will glow
brighter.
14) What happen if we give 220 volts dc supply to bulb or tube light?
- Bulbs or devices for AC are designed to
operate such that it offers high impedance to AC supply. Normally they
have low resistance. When DC supply is applied, due to low resistance,
the current through lamp would be so high that it may damage the bulb
element
15) What is meant by knee point voltage?
- Knee point voltage is calculated for
electrical Current transformers and is very important factor to choose a
CT. It is the voltage at which a CT gets saturated.
16) What is reverse power relay?
- Reverse Power flow relay are used in generating stations’ protection.
- A generating station is supposed to
feed power to the grid and in case generating units are off, there is no
generation in the plant then plant may take power from grid. To stop
the flow of power from grid to generator we use reverse power relay.
17) What will happen if DC supply is given on the primary of a transformer?
- Mainly transformer has high inductance
and low resistance. In case of DC supply there is no inductance, only
resistance will act in the electrical circuit. So high electrical
current will flow through primary side of the transformer. So for this
reason coil and insulation will burn out
- When AC current flow to primary winding
it induced alternating flux which also link to secondary winding so
secondary current flow in secondary winding according to primary
current.Secondary current also induced emf (Back emf) in secondary
winding which oppose induced emf of primary winding and thus control
primary current also.
- If DC current apply to Primary winding
than alternating flux is not produced so no secondary emf induced in
secondary winding so primary current may goes high and burn transformer
winding.
18) Different between megger and contact resistance meter?
- Megger used to measure cable
resistance, conductor continuity, phase identification where as contact
resistance meter used to measure low resistance like relays, contactors.
19) When we connect the capacitor bank in series?
- We connect capacitor bank in series to
improve the voltage profile at the load end in transmission line there
is considerable voltage drop along the transmission line due to
impedance of the line. so in order to bring the voltage at the load
terminals within its limits i.e (+ or – %6 )of the rated terminal
voltage the capacitor bank is used in series
20) What is Diversity factor in electrical installations?
- Diversity factor is the ratio of the
sum of the individual maximum demands of the various subdivisions of a
system, or part of a system, to the maximum demand of the whole system,
or part of the system, under consideration. Diversity factor is usually
more than one.
21) Why humming sound occurred in HT transmission line?
- This sound is coming due to ionization
(breakdown of air into charged particles) of air around transmission
conductor. This effect is called as Corona effect, and it is considered
as power loss.
22) Why frequency is 50 hz only & amp; why should we maintain the frequency constant?
- We can have the frequency at any
frequency we like, but then we must also make our own motors,
transformers or any other equipment we want to use.
- We maintain the frequency at 50 Hz or
60hz because the world maintains a standard at 50 /60hz and the
equipments are made to operate at these frequency.
23) If we give 2334 A, 540V
on Primary side of 1.125 MVA step up transformer, then what will be the
Secondary Current, If Secondary Voltage=11 KV?
- As we know the Voltage & current relation for transformer-V1/V2 = I2/I1
We Know, VI= 540 V; V2=11KV or 11000 V; I1= 2334 Amps.
By putting these value on Relation-
540/11000= I2/2334
So,I2 = 114.5 Amps
24) What are the points to be considered for MCB (miniature circuit breaker selection)?
- I(L)x1.25=I(MAX) maximum current. Mcb specification is done on maximum current flow in circuit.
25) How can we start-up the 40w tube light with 230v AC/DC without using any choke/Coil?
- It is possible by means of Electronic
choke. Otherwise it’s not possible to ionize the particles in tube.
Light, with normal voltage.
26) What is “pu” in electrical engineering?
- Pu stands for per unit and this will be
used in power system single line diagram there it is like a huge
electrical circuit with no of components (generators, transformers,
loads) with different ratings (in MVA and KV). To bring all the ratings
into common platform we use pu concept in which, in general largest MVA
and KV ratings of the component is considered as base values, then all
other component ratings will get back into this basis. Those values are
called as pu values. (p.u=actual value/base value).
27) Why link is provided in neutral of an ac circuit and fuse in phase of ac circuit?
- Link is provided at a Neutral common
point in the circuit from which various connections are taken for the
individual control circuit and so it is given in a link form to
withstand high Amps.
- But in the case of Fuse in the Phase of
AC circuit it is designed such that the fuse rating is calculated for
the particular circuit (i.e load) only. So if any malfunction happens
the fuse connected in the particular control circuit alone will blow
off.
- If Fuse is provided in Neutral and if
it is blowout and at the same time Supply is on than due to open or
break Neutral Voltage is increase and equipment may be damage.
28) If 200w, 100 w and 60 w lamps connected in series with 230V AC , which lamp glow brighter? Each lamp voltage rating is 230V.
- Each bulb when independently working will have currents (W/V= I)
- For 200 Watt Bulb current (I200) =200/230=0.8696 A
- For 100 Watt Bulb current (I100) =100/230=0.4348 A
- For 60 Watt Bulb current (I60) =60/230=0.2609 A
- Resistance of each bulb filament is (V/I = R)
- For 200 Watt Bulb R200= 230/0.8696= 264.5 ohms
- For 100 Watt Bulb R100= 230/0.4348 = 528.98 ohms and
- For 60 Watt Bulb R60= 230/0.2609=881.6 ohms respectively
- Now, when in series, current flowing in all bulbs will be same. The energy released will be I2R
- Thus, light output will be highest where resistance is highest. Thus, 60 watt bulb will be brightest.
- The 60W lamp as it has highest resistance & minimum current requirement.
- Highest voltage drop across it X I [which is common for all lamps] =s highest power.
- Note to remember:
- Lowest power-lamp has highest element resistance.
- And highest resistance will drop highest voltage drop across it in a Series circuit
- And highest resistance in a parallel
circuit will pass minimum current through it. So minimum power
dissipated across it as min current X equal Voltage across =s min power
dissipation
29) How to check Capacitor with use of Multi meter.
- Most troubles with Capacitors either open or short.
- An ohmmeter (multi meter) is good
enough. A shorted Capacitor will clearly show very low resistance. A
open Capacitor will not show any movement on ohmmeter.
- A good capacitor will show low
resistance initially, and resistance gradually increases. This shows
that Capacitor is not bad. By shorting the two ends of Capacitor
(charged by ohmmeter) momentarily can give a weak spark. To know the
value and other parameters, you need better instruments
30) What is the difference between Electronic regulator and ordinary rheostat regulator for fans?
- The difference between the electronic
and ordinary regulator is that in electronic regulator power losses are
less because as we decrease the speed the electronic regulator give the
power needed for that particular speed .But in case of ordinary rheostat
type regulator the power wastage is same for every speed and no power
is saved. In electronic regulator triac is employed for speed control.
by varying the firing angle speed is controlled but in rheostat control
resistance is decreased by steps to achieve speed control.
31) What will happen when power factor is leading in distribution of power?
- If there is high power factor, i.e if the power factor is close to one:
- Losses in form of heat will be reduced,
- Cable becomes less bulky and easy to carry, and very cheap to afford.
- It also reduces over heating of transformers.
32) What the main difference between UPS & amp; inverter?
- Uninterrupted power supply is mainly
use for short time. Means according to ups VA it gives backup. Ups is
also two types: on line and offline. Online ups having high volt and amp
for long time backup with high dc voltage. But ups start with 12v dc
with 7 amps. but inverter is start with 12v,24,dc to 36v dc and 120amp
to 180amp battery with long time backup
33) Which type of A.C motor is used in the fan?
- It is Single Phase induction motor which mostly squirrel cage rotor and are capacitor start capacitor run.
34) What is the difference between synchronous generator and asynchronous generator?
- In simple, synchronous generator
supplies’ both active and reactive power but asynchronous generator
(induction generator) supply’s only active power and observe reactive
power for magnetizing. This type of generators is used in windmills.
35) What is the Polarization index value?
- Its ratio between insulation resistance
(IR)i.e meager value for 10min to insulation resistance for 1 min. It
ranges from 5-7 for new motors & normally for motor to be in good
condition it should be Greater than 2.5 .
36) What is Automatic Voltage regulator (AVR)?
- AVR is an abbreviation for Automatic Voltage Regulator.
- It is important part in Synchronous
Generators; it controls the output voltage of the generator by
controlling its excitation current. Thus it can control the output
Reactive Power of the Generator.
37) Difference between a four point starter and three point starters?
- The shunt connection in four point
starter is provided separately from the line where as in three point
starter it is connected with line which is the drawback in three point
starter
38) What happens if we connect a capacitor to a generator load?
- Connecting a capacitor across a
generator always improves power factor, but it will help depends up on
the engine capacity of the alternator, otherwise the alternator will be
over loaded due to the extra watts consumed due to the improvement on
pf.
- Don’t connect a capacitor across an alternator while it is picking up or without any other load
39) Why the capacitors work on ac only?
- Generally capacitor gives infinite
resistance to dc components (i.e., block the dc components). It allows
the ac components to pass through.
40) Why the up to dia 70mm²
live conductor, the earth cable must be same size but above dia 70mm²
live conductor the earth conductor need to be only dia 70mm²?
- The current carrying capacity of a cable refers to it carrying a continuous load.
- An earth cable normally carries no load, and under fault conditions will carry a significant instantaneous current but only for a short time
most Regulations define 0.1 to 5 sec before the fuse or breaker trips.
Its size therefore is defined by different calculating parameters.
- The magnitude of earth fault current depends on:
- (a) the external earth loop impedance of the installation (i.e. beyond the supply terminals)
- (b) the impedance of the active conductor in fault
- (c) the impedance of the earth cable.
- i.e. Fault current = voltage / a + b + c
- Now when the active conductor (b) is
small, its impedance is much more than (a), so the earth (c) cable is
sized to match. As the active conductor gets bigger, its impedance drops
significantly below that of the external earth loop impedance (a); when
It is quite large its impedance can be ignored. At this point there is
no merit in increasing the earth cable size
- i.e. Fault current = voltage / a + c
- (c) is also very small so the fault current peaks out.
- The neutral conductor is a separate
issue. It is defined as an active conductor and therefore must be sized
for continuous full load. In a 3-phase system,
- If balanced, no neutral current flows.
It used to be common practice to install reduced neutral supplies, and
cables are available with say half-size neutrals (remember a neutral is
always necessary to provide single phase voltages). However the
increasing use of non-linear loads which produce harmonics has made this
practice dangerous, so for example the current in some standard require
full size neutrals. Indeed, in big UPS installations I install double
neutrals and earths for this reason.