Saturday, December 28, 2013

Selection of 3P-TPN-4P MCB & Distribution Board

Type of breakers based on number of pole:
  • Based on the number of poles, the breakers are classified as
  1. SP – Single Pole
  2. SPN – Single Pole and Neutral
  3. DP – Double pole
  4. TP – Triple Pole
  5. TPN – Triple Pole and Neutral
  6. 4P – Four Pole
1.     SP ( Single Pole ) MCB:
  • In Single Pole MCCB, switching & protection is affected in only one phase.
  • Application: Single Phase Supply to break the Phase only.
2.     DP ( Double Pole ) MCB:
  • In Two Pole MCCB, switching & protection is affected in phases and the neutral.
  • Application: Single Phase Supply to break the Phase and Neutral.
3.     TP ( Triple Pole) MCB:
  • In Three Pole MCB, switching & protection is affected in only three phases and the neutral is not part of the MCB.
  • 3pole MCCB signifies for the connection of three wires for three phase system (R-Y-B Phase).
  • Application: Three Phase Supply only (Without Neutral).
4.     TPN (3P+N) MCB:
  • In TPN MCB, Neutral is part of the MCB as a separate pole but without any protective given in the neutral pole (i.e.) neutral is only switched but has no protective element incorporated.
  • TPN for Y (or star) the connection between ground and neutral is in many countries not allowed. Therefore the N is also switches.
  • Application: Three Phase Supply with Neutral
5.     4 Pole MCB:
  • 4pole MCCB for 4 wires connections, the one additional 4th pole for neutral wire connection so that between neutral and any of the other three will supply.
  • In 4-Pole MCCBs the neutral pole is also having protective release as in the phase poles.
  • Application: Three Phase Supply with Neutral

Difference between TPN and 4P (or SPN and DP):

  • TPN means a 4 Pole device with 4th Pole as Neutral. In TPN opening & closing will open & close the Neutral.
  • For TPN, protection applies to the current flows through only 3 poles (Three Phase) only; there is no protection for the current flow through the neutral pole. Neutral is just an isolating pole.
  • TP MCB is used in 3phase 4wire system. It is denoted as TP+N which will mean a three pole device with external neutral link which can be isolated if required. 
  • For the 4 pole breakers, protection applies to current flow through all poles. However when breaker trips or manually opened, all poles are disconnected.
  • Same type of difference also applies for SPN and DP.

Where to Use TP, TPN and 4P in Distribution panel:

  • For any Distribution board, the protection system (MCB) must be used in the incomer. For a three phase distribution panel either TP or TPN or 4P can be used as the incoming protection.
  • TP MCB: It is most commonly used type in all ordinary three phase supply.
  • TPN MCB: It is generally used where there are dual sources of incomer to the panel (utility source and emergency generator source).
  • 4P MCB: It is used where is the possibility of high neutral current (due to unbalance loads and /or 3rd and multiple of 3rd harmonics current etc) and Neutral / Earth Protection is provided on Neutral.

Where to use 4 Pole or TPN MCB instead of 3 Pole (TP) MCB.

  • Multiple Incoming Power System:
  • When we have a transformer or a stand-by generator feeding to a bus, it is mandatory that at least either of the Incomers or the bus coupler must be TPN or 4-Pole Breaker please refers IS 3043.
  • In multi incomer power feeding systems, we cannot mix up the neutrals of incoming powers to other Power Source so we can use TPN or 4P breakers or MCB instead of TP MCB to isolate the Neutral of other power sources from the Neutral of incomer power in use.
  • We can use 4 Pole ACB instead of TP for safety reasons .If there is power failure and DG sets are in running condition to feed the loads, if there is some unbalance in loads(which is practically unavoidable in L.V. distribution system ), depending of quantum of unbalance, there will be flow of current through Neutral. During this time, if Power Supply Utility Technicians are working, and if they touch the neutral conductors(which is earthed at their point ) they will likely to get electric shock depending on the potential rise in common neutral due flow of current through Neutral conductor as stated above. Even fatal accident may occur due the above reason. As such, it is a mandatory practice to isolate the two Neutrals.
  • We can use 4-pole breakers or TPN Breakers when the system has two alternative sources and, in the event of power failure from the mains, change-over to the standby generator is done. In such a case, it is a good practice to isolate the neutral also.
  • 4 pole circuit breakers have advantages in the case when one of the poles of the device will get damage, and it also provides isolation from neutral voltage.
  • Normally, Neutral is not allowed to break in any conditions, (except special applications) for human & equipment safety. So for single incomer power fed systems, 3P breaker is used, where only phases are isolated during breaking operations.
  • Where We have dual Power like in DG & other electricity supply sources ,it is required to isolate neutral, where neutral needs to be isolated  in internal network TPN MCB or 4P MCB can be used.

Where to use 4 Pole MCB instead of TPN MCB

  • Any Protection Relay used on Neutral (Ground Fault Protection of Double ended System):
  • The use of four poles or three poles CB will depend on system protection and system configuration.
  • Normally in 3phase with neutral we just use 3pole CB and Neutral is connected on common Neutral Link but if application of 3pole will affect the operation of protective relay then we must use 4pole CB.
  • System evaluation has to be required to decide whether three-pole circuit breakers plus neutral link can be used or four-pole breakers are required.
  • If unrestricted ground fault protection is fitted to the transformer neutral, then the bus section circuit breaker should have 4-poles and preferably incomer circuit breakers should also have 4-poles because un cleared ground fault located at the load side of a feeder have two return paths. As shown in fig a ground fault on a feeder at the bus section “A” will have a current return path in both the incomers, thus tripping both Bus. The sensitivity of the unrestricted ground fault relay is reduced due to the split current paths.
Untitled
  • For System Stability :
  • In an unbalanced 3phase system or a system with non-linear loads, the neutral gives the safety to the unbalanced loads in the system and therefore It must not be neglected. In perfectly balanced conditions the neutral functions as a safety conductor in the unforeseen short-circuit and fault conditions. Therefore by using 4-pole MCB will enhance the system stability.
  • 4 Poles will be decided after knowing the Earthing Systems (TT, TN-S, TN-C, IT).
(1) IT (with distributed neutral) System:
  • The Neutral should be switched on & off with phases.
  • Required MCB: TPN or 4P MCB.
(2) IT (without distributed neutral) System:
  • There is no neutral.
  • Required MCB: TP MCB.
(3) TN-S System:
  • Required MCB: TP MCB because even when neutral is cut off system remains connected with Ground.
(4) TN-C System:
  • Required MCB: TPN or 4P only, because we cannot afford to cut neutral doing so will result in system loosing contact with Ground.
(5) TN-C-S System:
  • Neutral and Ground cable are separate
  • Required MCB:  TP MCB Because Neutral and Ground cable are separate.
(6) TT System
  • Ground is provided locally
  • Required MCB:  TP MCB because ground is provided locally.
  • Conclusion: Its compulsory to use TPN in TN-C system rest everywhere you can use MCB.

Nomenclature of Distribution Board:

  • Distribution Box can be decided by “way” means how many how many single phase (single pole) distribution. Circuit and Neutral are used.

1)     SPN Distribution Board (Incoming+ Outgoing)

  • 4way (Row) SPN = 4 X 1SP= 4Nos (Module) of single pole MCB as outgoing feeders.
  • 6way (Row) SPN = 6 X 1SP= 6Nos (Module) of single pole MCB as outgoing feeders.
  • 8way (Row) SPN = 8 X 1SP= 8Nos (Module) of single pole MCB as outgoing feeders.
  • 10way (Row) SPN = 10 X 1SP= 10Nos (Module) of single pole MCB as outgoing feeders.
  • 12way (Row) SPN = 12 X 1SP= 12Nos (Module) of single pole MCB as outgoing feeders.
  • Normally single phase distribution is mainly used for small single phase loads at house wiring or industrial lighting wiring.

2)     TPN Distribution Board (Incoming, Outgoing)

  • 4way (Row) TPN = 4 X TP= 4nos of 3pole MCB as outgoing feeders =12 No of single pole MCB.
  • 6way (Row) TPN = 6 X TP= 6nos of 3pole MCB as outgoing feeders =18 No of single pole MCB.
  • 8way (Row) TPN = 8 X TP= 8nos of 3pole MCB as outgoing feeders =24 No of single pole MCB.
  • 10way (Row) TPN = 10 X TP= 10nos of 3pole MCB as outgoing feeders =30 No of single pole MCB.
  • 12way (Row) TPN =12 X TP= 12nos of 3pole MCB as outgoing feeders =36 No of single pole MCB

Wednesday, December 25, 2013

How to save Electrical energy at Home

How to save  Electrical energy at Home

In our home we use lot of electrical equipment like Tv, Freeze, Washing machine,Mp3 player. music system, computer laptop. But we have not adequate knowledge for how to use this electrical equipment in proper way Due to this ignorance we are paying more electricity Bill which we are not actually use.
Do you know in actual we are consuming more electricity or paying more amounts what we actually not use it?
According to the energy auditors we can easily save between 5 and 10% of their energy consumption (and costs) by changing our behavior such as switching electrical equipment off at the mains rather than leaving it on standby, turning off lights when they’re not being used
By saving Electrical energy will directly reflected to saving money so it is very necessary to under stood ghost unit or amount which we are paying without using the appliances.
The major appliances in your home — refrigerators, clothes washers, dishwashers — account for a big chunk of your monthly utility bill. And if your refrigerator or washing machine is more than a decade old, you’re spending a lot more on energy than you need to.
Today’s major appliances don’t hog energy the way older models do because they must meet minimum federal energy efficiency standards. These standards have been tightened over the years, so any new appliance you buy today has to use less energy than the model you’re replacing. For instance, if you buy one of today’s most energy-efficient refrigerators, it will use less than half the energy of a model that’s 12 years old or older.

Lighting

  • Get into the habit of turning lights off when you leave a room. —-Saving Energy 0.5 %
  • Use task lighting (table and desktop lamps) instead of room lighting.
  • Take advantage of daylight
  • De-dust lighting fixtures to maintain illumination—–Saving Energy 1 %
  • Compact fluorescent bulbs (CFL):
  1. CFL use 75% less energy than Normal bulbs.
  2. CFL are four times more energy efficient than Normal bulbs.
  3. CFL can last up to ten times longer than a normal bulb.
  • Use electronic chokes. in place of conventional copper chokes.—-Saving Energy 2 %
  • Get into the habit of turning lights off when you leave a room.
  • Use only one bulb for light fittings with more than one light bulb, or replace additional bulbs with a lower wattage version.
  • Use energy-saving light bulbs that can last up to ten times longer than a normal bulb and use significantly less energy. A single 20- to 25-watt energy-saving bulb provides as much light as a 100-watt ordinary bulb.
  • Use tungsten halogen bulbs for spotlights—they last longer and are up to 100% more efficient.
  • Fit external lights with a motion sensor.
  • Use high frequency fittings for fluorescent tubes because they cut flicker and are even more efficient than energy-saving light bulbs. They are suitable for kitchens, halls, workshops and garages.

Save on Your Fridge & Freezer:

  • Defrost your fridge regularly.
  • Check that the door seals are strong and intact.
  • Don’t stand Freezer’s Back Side too near the Wall.
  • Avoid putting warm or hot food in the fridge or freezer—it   requires more energy to cool it down.
  • Clean condenser coils twice a year.
  • Get rid of old refrigerators!  They use twice the energy as new Energy Star® models.
  • Keep refrigerators full but not overcrowded.
  • Defrost your fridge regularly. When ice builds up, your freezer uses more electricity. If it frosts up again quickly, check that the door seals are strong and intact.
  • Do not stand the fridge next to the oven or other hot appliances if you can help it. Also ensure there is plenty of ventilation space behind and above it.
  • Keep the fridge at 40°F and the freezer at 0°F. Empty and then turn your fridge off if you go on a long vacation (but make sure you leave the door open).
  • Aim to keep your fridge at least three-quarters full to maintain maximum efficiency. A full fridge is a healthy fridge.
  • Avoid putting warm or hot food in the fridge or freezer—it requires more energy to cool it down.

AIR CONDITION UNIT

  • For Home Purpose use Window unit Instead Of Split Unit.
  • For Office and Commercial Purpose Use Split AC instead of Window unit.
  • Consider installing a programmable t. Just set the times and temperatures to match your schedule and you will save money and be comfortably cool when you return home.
  • Get air conditioner maintenance each year.
  • Checks the condenser coils, the evaporator coils, the blower wheel, the filter, the lubrication and the electrical   contacts.
  • Replace worn and dirty equipment for maximum efficiency.
  • Replace air conditioner filters every month.
  • Turn off central air conditioning 30 minutes before leaving your home.
  • Consider using ceiling or portable fans to circulate and cool the air.
  • Try increasing your air conditioner temperature. Even 1 degree higher could mean significant savings, and you will probably not notice the difference.
  • Keep central air conditioner usage to a minimum—or even turn the unit off—if you plan to go away.
  • Consider installing a programmable thermostat. Just set the times and temperatures to match your schedule, and you will save money and be comfortably cool when you return home.
  • Get air conditioner maintenance each year—ensure your service person checks the condenser coils, the evaporator coils, the blower wheel, the filter, the lubrication and the electrical contacts. Replace worn and dirty equipment for maximum efficiency.
  • Replace air conditioner filters every month.
  • Buy the proper size equipment to meet your family’s needs—an oversized air conditioner unit will waste energy.
  • If you have a furnace, replace it at the same time as your air conditioner system. Why? Because it is your furnace fan that blows cool air around your home, and a newer furnace fan provides improved air circulation all year round, plus saves energy costs.

Water Heater:

  • Check your hot water temperature. It does not need to be any higher than 140°F for washing purposes.
  • Plug the basin or bath when you run any hot water.
  • Use a timer to make sure the heating and hot water are only on when needed.
  • Insulate your hot water pipes to prevent heat loss, and your water will stay hotter for longer. Plus, you will also use less energy to heat it. And simply fitting a jacket onto your hot water tank can cut waste by up to three quarters.
  • Take showers—a bath consumes 5 times more hot water. Buy a low-flow showerhead for more efficiency and it will pay for itself in no time.
  • Avoid washing dishes under hot running water, and do not pre-rinse before using the dishwasher.
  • Repair dripping hot water taps immediately
  • Make sure hot water taps are always turned off properly.

Washing Machine:

  • Wash full loads of Washing Machine—you will use your machine less often, saving time, and it is more energy-efficient.
  • Wash at a lower temperature or the economy setting to save even more.
  • Use the spin cycle, and then hang washing out rather than tumble drying—your clothes and linens will smell fresher!
  • If you need to tumble dry, try a lower temperature setting.
  • Use your dryer for consecutive loads, because the built-up heat between loads will use less energy.

Oven/Electrical Cooker:

  • Make sure your oven door closes tightly.
  • Use a microwave rather than conventional oven, when possible.
  • Keep the center of the pan over the element, and keep the lid on when cooking on the stovetop.
  • Only boil the amount of water that you need—just ensure there is enough water to cover the heating element. Turn the element or electric kettle down as soon as it reaches the boiling point.

COMPUTER / LAPTOP

  • Buy a laptop instead of a desktop, if practical. —-Saving Energy 5 %.
  • If you buy a desktop, get an LCD screen instead of an outdated CRT.
  • Use sleep-mode when not in use helps cut  energy costs by approx  40%.
  • Turn off the monitor; this device alone uses more than half  the system’s  energy.
  • Screen savers save computer screens, not energy.
  • Use separate  On/Off switch Socket Instead of One.
  • Laser printers use more electricity than inkjet printers.

FAN:

  • A ceiling fan in operation through out night will gobble up 22 units in a month.
  • There is a wrong notion that fan at more speed would consume more current.
  • Fan running at slow speed would waste energy as heat in the regulator.
  • The ordinary regulator would take 20 watts extra at low speed.
  • The energy loss can be compensated by using  electronic   regulator

Buy efficient electric appliances:

  • They use two to 10 times less electricity for the same functionality, and are mostly higher quality products that last longer than the less efficient ones. In short, efficient appliances save you lots of energy and money.
  • In many countries, efficiency rating labels are mandatory on most appliances. Look Energy Star label is used.
  • The label gives you information on the annual electricity consumption. In the paragraphs below, we provide some indication of the consumption of the most efficient appliances to use as a rough guide when shopping. Lists of brands and models and where to find them are country-specific and so cannot be listed here, but check the links on this page for more detailed information.
  • Average consumption of electric appliances in different regions in the world, compared with the high efficient models on the market

Ghost consumers:

  • Identify the “ghost consumers” which consume power – not because they are in use, but because they are   plugged in and are in stand-by mode.
  • The TV consumes 10 watt power When It’s is in Stand by Mode.
Ex.  TV is in stand-by-mode  for 10 hours a Day.
Energy Consumption  /  Day= 10 X 10 = 100 Watts. = 0.1 KWH.
Energy consumption /  Month= 1X100X30=3000 Watts=3KWH ( Unit) .
Energy Consumption in Rupees. = 3 X 4 = 12 Rs/Month.
  • The TV consumes 5 watt power when we  don’t  plug out from switch Board.
Ex.  TV is in un Plug Mode for 10 hours a Day.
Energy Consumption  /  Day= 5 X 10 = 50 Watts. = 0.05 KWH.
Energy consumption /  Month= 1X50X30= 1500 Watts=1.5 KWH ( Unit) .
Energy Consumption in Rupees. = 1.5 X 4 = 6 Rs/Month.
  • The cell phone charger uses 3 watt per hour when plugged.
  • Mosquito mats consume 5 watts per hour.
  • If you use an electric geyser, do not leave it in thermostat mode, for it causes standing losses of 1-1.5 units

Calculate Size of Contactor, Fuse, C.B, O/L  of DOL Starter

  • Calculate Size of each Part of DOL starter for The System Voltage 415V ,5HP Three Phase House hold Application Induction Motor ,Code A, Motor efficiency 80%,Motor RPM 750 ,Power Factor 0.8 , Overload Relay of Starter is Put before Motor.

Basic Calculation of Motor Torque & Current:

  • Motor Rated Torque (Full Load Torque) =5252xHPxRPM
  • Motor Rated Torque (Full Load Torque) =5252x5x750=35 lb-ft.
  • Motor Rated Torque (Full Load Torque) =9500xKWxRPM
  • Motor Rated Torque (Full Load Torque) =9500x(5×0.746)x750 =47 Nm
  • If Motor Capacity is less than 30 KW than Motor Starting Torque is 3xMotor Full Load Current or 2X Motor Full Load Current.
  • Motor Starting Torque=3xMotor Full Load Current.
  • Motor Starting Torque==3×47=142Nm.
  • Motor Lock Rotor Current =1000xHPx figure from below Chart/1.732×415
Locked Rotor Current
Code
Min
Max
A
1
3.14
B
3.15
3.54
C
3.55
3.99
D
4
4.49
E
4.5
4.99
F
5
2.59
G
2.6
6.29
H
6.3
7.09
I
7.1
7.99
K
8
8.99
L
9
9.99
M
10
11.19
N
11.2
12.49
P
12.5
13.99
R
14
15.99
S
16
17.99
T
18
19.99
U
20
22.39
V
22.4
  • As per above chart Minimum Locked Rotor Current  =1000x5x1/1.732×415=7 Amp
  • Maximum Locked Rotor Current =1000x5x3.14/1.732×415=22 Amp.
  • Motor Full Load Current (Line) =KWx1000/1.732×415
  • Motor Full Load Current (Line) = (5×0.746)x1000/1.732×415=6 Amp.
  • Motor Full Load Current (Phase)=Motor Full Load Current (Line)/1.732
  • Motor Full Load Current (Phase)==6/1.732=4Amp
  • Motor Starting Current =6 to 7xFull Load Current.
  • Motor Starting Current (Line)=7×6=45 Amp

(1) Size of Fuse:

Fuse  as per NEC 430-52
Type of Motor Time Delay Fuse Non-Time Delay Fuse
Single Phase
300%
175%
3 Phase
300%
175%
Synchronous
300%
175%
Wound Rotor
150%
150%
Direct Current
150%
150%
  • Maximum Size of Time Delay Fuse =300% x Full Load Line Current.
  • Maximum Size of Time Delay Fuse =300%x6= 19 Amp.
  • Maximum Size of Non Time Delay Fuse =1.75% x Full Load Line Current.
  • Maximum Size of Non Time Delay Fuse=1.75%6=11 Amp.

(2) Size of Circuit Breaker:

Circuit Breaker as per NEC 430-52
Type of Motor Instantaneous Trip Inverse Time
Single Phase
800%
250%
3 Phase
800%
250%
Synchronous
800%
250%
Wound Rotor
800%
150%
Direct Current
200%
150%
  • Maximum Size of Instantaneous Trip Circuit Breaker =800% x Full Load Line Current.
  • Maximum Size of Instantaneous Trip Circuit Breaker =800%x6= 52 Amp.
  • Maximum Size of Inverse Trip Circuit Breaker =250% x Full Load Line Current.
  • Maximum Size of Inverse Trip Circuit Breaker =250%x6= 16 Amp.

(3) Thermal over Load Relay:

  • Thermal over Load Relay (Phase):
  • Min Thermal Over Load Relay setting =70%xFull Load Current(Phase)
  • Min Thermal Over Load Relay setting =70%x4= 3 Amp
  • Max Thermal Over Load Relay setting =120%xFull Load Current(Phase)
  • Max Thermal Over Load Relay setting =120%x4= 4 Amp
  • Thermal over Load Relay (Phase):
  • Thermal over Load Relay setting =100%xFull Load Current (Line).
  • Thermal over Load Relay setting =100%x6= 6 Amp

(4) Size and Type of Contactor:

Application
Contactor
Making Cap
Non-Inductive or Slightly Inductive ,Resistive Load
AC1
1.5
Slip Ring Motor
AC2
4
Squirrel Cage Motor
AC3
10
Rapid Start / Stop
AC4
12
Switching of Electrical Discharge Lamp
AC5a
3
Switching of Electrical Incandescent Lamp
AC5b
1.5
Switching of Transformer
AC6a
12
Switching of Capacitor Bank
AC6b
12
Slightly Inductive Load in Household or same type load
AC7a
1.5
Motor Load in Household Application
AC7b
8
Hermetic refrigerant Compressor Motor with Manual O/L Reset
AC8a
6
Hermetic refrigerant Compressor Motor with Auto O/L Reset
AC8b
6
Control of Restive & Solid State Load with opto coupler Isolation
AC12
6
Control of Restive Load and Solid State with T/C Isolation
AC13
10
Control of Small Electro Magnetic Load ( <72va span="">
AC14
6
Control of Small Electro Magnetic Load ( >72VA)
AC15
10
  • As per above Chart
  • Type of Contactor= AC7b
  • Size of Main Contactor = 100%X Full Load Current (Line).
  • Size of Main Contactor =100%x6 = 6 Amp.
  • Making/Breaking Capacity of Contactor= Value above Chart x Full Load Current (Line).
  • Making/Breaking Capacity of Contactor=8×6= 52 Amp.

Tuesday, December 24, 2013

Electrical Thumb Rules (Part 1)

Electrical Thumb Rules For:

  • Cable Capacity
  • Current Capacity of Equipment
  • Earthing Resistance
  • Minimum Bending Radius
  • Insulation Resistance
  • Lighting Arrestor
  • Transformer
  • Diesel Generator
  • Current Transformer
  • Quick Electrical Calculation
  • Cable Capacity
  • For Cu Wire Current Capacity (Up to 30 Sq.mm) = 6X Size of Wire in Sq.mm
    Ex. For 2.5 Sq.mm = 6×2.5 = 15 Amp, For 1 Sq.mm = 6×1 = 6 Amp, For 1.5 Sq.mm = 6×1.5 = 9 Amp
  • For Cable Current Capacity = 4X Size of Cable in Sq.mm, Ex. For 2.5 Sq.mm = 4×2.5 = 9 Amp.
  • Nomenclature for cable Rating = Uo/U
  • where Uo = Phase-Ground Voltage, U = Phase-Phase Voltage, Um = Highest Permissible Voltage

Current Capacity of Equipment

  • 1 Phase Motor draws Current = 7Amp per HP.
  • 3 Phase Motor draws Current = 1.25Amp per HP.
  • Full Load Current of 3 Phase Motor = HPx1.5
  • Full Load Current of 1 Phase Motor = HPx6
  • No Load Current of 3 Phase Motor = 30% of FLC
  • KW Rating of Motor = HPx0.75
  • Full Load Current of equipment = 1.39xKVA (for 3 Phase 415Volt)
  • Full Load Current of equipment = 1.74xKw (for 3 Phase 415Volt)


Earthing Resistance

  • Earthing Resistance for Single Pit = 5Ω, Earthing Grid = 0.5Ω
  • As per NEC 1985 Earthing Resistance should be < 5Ω.
  • Voltage between Neutral and Earth <= 2 Volt
  • Resistance between Neutral and Earth <= 1Ω
  • Creepage Distance = 18 to 22mm/KV (Moderate Polluted Air) or
  • Creepage Distance = 25 to 33mm/KV (Highly Polluted Air)


Minimum Bending Radius

  • Minimum Bending Radius for LT Power Cable = 12 x Dia of Cable.
  • Minimum Bending Radius for HT Power Cable = 20 x Dia of Cable.
  • Minimum Bending Radius for Control Cable = 10 x Dia of Cable.


Insulation Resistance

  • Insulation Resistance Value for Rotating Machine = (KV+1) MΩ.
  • Insulation Resistance Value for Motor (IS 732) = ((20xVoltage (L-L)) / (1000+ (2xKW)).
  • Insulation Resistance Value for Equipment (<1kv strong=""> Minimum 1 MΩ.
  • Insulation Resistance Value for Equipment (>1KV) = KV 1 MΩ per 1KV.
  • Insulation Resistance Value for Panel = 2 x KV rating of the panel.
  • Min Insulation Resistance Value (Domestic) = 50 MΩ / No of Points. (All Electrical Points with Electrical fitting & Plugs). Should be less than 0.5 MΩ
  • Min Insulation Resistance Value (Commercial) = 100 MΩ / No of Points. (All Electrical Points without fitting & Plugs).Should be less than 0.5 MΩ.
  • Test Voltage (A.C) for Meggering = (2X Name Plate Voltage) +1000
  • Test Voltage (D.C) for Meggering = (2X Name Plate Voltage).
  • Submersible Pump Take 0.4 KWH of extra Energy at 1 meter drop of Water.

Lighting Arrestor

Arrestor have Two Rating:
  1. MCOV=Max. Continuous Line to Ground Operating Voltage.
  2. Duty Cycle Voltage. (Duty Cycle Voltage > MCOV).


Transformer

  • Current Rating of Transformer = KVA x 1.4
  • Short Circuit Current of T.C /Generator = Current Rating / % Impedance
  • No Load Current of Transformer =< 2% of Transformer Rated current
  • Capacitor Current (Ic) = KVAR / 1.732xVolt (Phase-Phase)
  • Typically the local utility provides transformers rated up to 500kVA For maximum connected load of 99kW,
  • Typically the local utility provides transformers rated up to 1250kVA For maximum connected load of 150kW.
  • The diversity they would apply to apartments is around 60%
  • Maximum HT (11kV) connected load will be around 4.5MVA per circuit.
  • 4No. earth pits per transformer (2No. for body and 2No. for neutral earthing),
  • Clearances, approx.1000mm around TC allow for transformer movement for replacement.

Diesel Generator

  • Diesel Generator Set Produces = 3.87 Units (KWH) in 1 Litter of Diesel.
  • Requirement Area of Diesel Generator = for 25KW to 48KW = 56 Sq.meter, 100KW = 65 Sq.meter.
  • DG less than or equal to 1000kVA must be in a canopy.
  • DG greater 1000kVA can either be in a canopy or skid mounted in an acoustically treated room
  • DG noise levels to be less than 75dBA at 1 meter.
  • DG fuel storage tanks should be a maximum of 990 Litter per unit. Storage tanks above this level will trigger more stringent explosion protection provision.

Current Transformer

Nomenclature of CT:
  • Ratio: input / output current ratio
  • Burden (VA): total burden including pilot wires. (2.5, 5, 10, 15 and 30VA.)
  • Class: Accuracy required for operation (Metering: 0.2, 0.5, 1 or 3, Protection: 5, 10, 15, 20, 30).
  • Accuracy Limit Factor:
  • Nomenclature of CT: Ratio, VA Burden, Accuracy Class, Accuracy Limit Factor.Example: 1600/5, 15VA 5P10  (Ratio: 1600/5, Burden: 15VA, Accuracy Class: 5P, ALF: 10)
  • As per IEEE Metering CT: 0.3B0.1 rated Metering CT is accu­rate to 0.3 percent if the connected secondary burden if imped­ance does not exceed 0.1 ohms.
  • As per IEEE Relaying (Protection) CT: 2.5C100 Relaying CT is accurate within 2.5 percent if the secondary burden is less than 1.0 ohm (100 volts/100A).


Quick Electrical Calculation

1HP = 0.746KWStar Connection
1KW = 1.36HPLine Voltage = √3 Phase Voltage
1Watt = 0.846 Kla/HrLine Current = Phase Current
1Watt = 3.41 BTU/HrDelta Connection
1KWH = 3.6 MJLine Voltage = Phase Voltage
1Cal = 4.186 JLine Current = √3 Phase Current
1Tone = 3530 BTU
85 Sq.ft Floor Area = 1200 BTU
1Kcal = 4186 Joule
1KWH = 860 Kcal
1Cal = 4.183 Joule

Electrical Thumb Rules (Part 2)

Electrical Thumb Rules

Useful Electrical Equations

  • For Sinusoidal Current: Form Factor = RMS Value/Average Value =1.11
  • For Sinusoidal Current: Peak Factor = Max Value/RMS Value = 1.414
  • Average Value of Sinusoidal Current (Iav) = 0.637 x Im (Im = Max.Value)
  • RMS Value of Sinusoidal Current (Irms) = 0.707 x Im (Im = Max.Value)
  • A.C Current = D.C Current/0.636.
  • Phase Difference between Phase = 360/ No of Phase (1 Phase=230/1=360°, 2 Phase=360/2=180°)
  • Short Circuit Level of Cable in KA (Isc) =
    (
    0.094 x Cable Dia in Sq.mm) /√ Short Circuit Time (Sec)
  • Max.Cross Section Area of Earthing Strip (mm2) = √(Fault Current x Fault Current x Operating Time of Disconnected Device ) / K
    K = Material Factor, K for Cu = 159, K for Al = 105, K for steel = 58 , K for GI = 80
  • Most Economical Voltage at given Distance = 5.5x√((km/1.6)+(kw/100))
  • Cable Voltage Drop (%) =
    (
    1.732 x current x (RcosǾ+jsinǾ) x 1.732 x Length (km) x 100) / (Volt(L-L) x Cable Run.
  • Spacing of Conductor in Transmission Line (mm) = 500 + 18 x (P – P Volt) + (2 x (Span in Length)/50).
  • Protection radius of Lighnting Arrestor = √h x (2D-h) + (2D+L).
    Where h= height of L.A, D-distance of equipment (20, 40, 60 Meter), L=V x t (V=1m/ms, t=Discharge Time).
  • Size of Lightning Arrestor = 1.5x Phase to Earth Voltage or 1.5 x (System Voltage/1.732).
  • Maximum Voltage of the System = 1.1xRated Voltage (Ex. 66KV = 1.1 × 66 = 72.6KV)
  • Load Factor = Average Power/Peak Power
  • If Load Factor is 1 or 100% = This is best situation for System and Consumer both.
  • If Load Factor is Low (0 or 25%) = you are paying maximum amount of KWH consumption. Load Factor may be increased by switching or use of your Electrical Application.
  • Demand Factor = Maximum Demand / Total Connected Load (Demand Factor <1 li="">
  • Demand factor should be applied for Group Load
  • Diversity Factor =
    Sum of Maximum Power Demand / Maximum Demand (Demand Factor >1)
    Diversity factor should be consider for individual Load
  • Plant Factor (Plant Capacity) = Average Load / Capacity of Plant
  • Fusing Factor = Minimum Fusing Current / Current Rating (Fusing Factor>1).
  • Voltage Variation (1 to 1.5%) = ((Average Voltage – Min Voltage) x 100)/Average Voltage
    Ex: 462V, 463V, 455V, Voltage Variation= ((460 – 455)  x 100)/455 = 1.1%.
  • Current Variation (10%) = ((Average Current – Min Current) x 100)/Average Current
    Ex: 30A,35A,30A, Current Variation = ((35-31.7) x 100)/31.7 = 10.4%
  • Fault Level at TC Secondary
    = TC (VA) x 100 / Transformer Secondary (V) x Impedance (%)
  • Motor Full Load Current = Kw /1.732 x KV x P.F x Efficiency

Electrical Thumb Rules (Part 3)

Electrical Thumb Rules

Size of Capacitor for Power Factor Correction

For Motor
Size of Capacitor = 1/3 Hp of Motor ( 0.12x KW of Motor)
For Transformer
< 315 KVA5% of KVA Rating
315 KVA to 1000 KVA6% of KVA Rating
>1000 KVA8% of KVA Rating

Earthing Resistance value

Earthing Resistance Value
Power Station0.5 Ω
Sub Station Major1.0 Ω
Sub Station Minor2.0 Ω
Distribution Transformer5.0 Ω
Transmission Line10 Ω
Single Isolate Earth Pit5.0 Ω
Earthing Grid0.5 Ω
As per NEC Earthing Resistance should be <5 .0="" strong="">

Voltage Limit (As per CPWD & KEB)

Voltage Limit (As Per CPWD)
240V< 5 KW
415V<100 kva="" td="">
11KV<3 nbsp="" td="">
22KV<6 mva="" td="">
33KV<12 mva="" td="">
66KV<20 mva="" td="">
110KV<40 mva="" td="">
220KV>40 MVA

Voltage Variation

> 33 KV(-) 12.5% to (+) 10%
< 33 KV(-) 9% to (+) 6%
Low Voltage(-) 6% to (+) 6%

Insulation Class

InsulationTemperature
Class A105°C
Class E120°C
Class B130°C
Class F155°C
Class H180°C
Class N200°C

Standard Voltage Limit

VoltageIEC (60038)IEC (6100:3.6)Indian Elect. Rule
ELV< 50 V

LV50 V to 1 KV<=1 KV< 250 V
MV
<= 35 KV250 V to 650 V
HV> 1KV<= 230 KV650 V to 33 KV
EHV
> 230 KV> 33 KV

Standard Electrical Connection (As per GERC)

As per Type of Connection
ConnectionVoltage
LT Connection<=440V
HT connection440V to 66KV
EHT connection>= 66KV
As per Electrical Load Demand
Up 6W Load demand1 Phase 230V Supply
6W to 100KVA(100KW)3 Phase 440V Supply
100KVA to 2500KVA11KV,22KV,33KV
Above 2500KVA66KV
HT Connection Earthing
H.T Connection’s Earthing Strip20mmX4mm Cu. Strip
CT & PT bodies2Nos
PT Secondary1Nos
CT Secondary1Nos
I/C and O/G Cable+ Cubicle Body2Nos

Standard Meter Room Size (As per GERC)

Meter Box HeightUpper level does not beyond 1.7 meter and Lower level should not below 1.2 meter from ground.
Facing of Meter BoxMeter Box should be at front area of Building at Ground Floor.
Meter Room / Closed Shade4 meter square Size

Electrical Load as per Sq.ft Area (As per DHBVN)

Sq.ft AreaRequired Load (Connected)
< 900 Sq.ft8 KW
901 Sq.ft to 1600 Sq.ft16 KW
1601 Sq.ft to 2500 Sq.ft20 KW
> 2500 Sq.ft24 KW
For Flats :100 Sq.ft / 1 KW
For Flats USS /TC: 100 Sq.ft / 23 KVA

Contracted Load in case of High-rise Building

For Domestic Load500 watt per 100 Sq. foot of the constructed area.
For Commercial1500 watt per 100 Sq. foot of the constructed area
Other Common LoadFor lift, water lifting pump, streetlight if any, corridor/campus lighting and other common facilities, actual load shall be calculated
Staircase Light11KW/Flat Ex: 200Flat=200×11=2.2KW
Sanctioned Load for Building
Up to 50 kWThe L.T. existing mains shall be strengthened.
50 kW to 450 kW (500 kVA)11 kV existing feeders shall be extended if spare capacity is available otherwise, new 11 kV feeders shall be constructed.
450 kW to 2550 kW (3000 kVA)11 kV feeder shall be constructed from the nearest 33 kV or 110 kV substation
2550 kW to 8500 kW (10,000 kVA)33kV feeder from 33 kV or 110 kV sub station
8500 kW (10,000 kVA)110 kV feeder from nearest 110 kV or 220 kV sub-station

Electrical Thumb Rule (Part 4)

Electrical Thumb Rules (Part 4)

1. Substation Capacity and Short Circuit Current Capacity

As per GERC
Voltage Sub Station CapacityShort Circuit Current
400 KVUp to 1000 MVA40 KA  (1 to 3 Sec)
220 KVUp to 320 MVA40 KA  (1 to 3 Sec)
132 KVUp to 150 MVA32 KA  (1 to 3 Sec)
66 KVUp to 80 MVA25 KA  (1 to 3 Sec)
33 KV1.5 MVA to 5 MVA35 KA (Urban) (1 to 3 Sec)
11 KV150 KVA to 1.5 MVA25 KA (Rural) (1 to 3 Sec)
415 V6  KVA to 150 KVA10 KA  (1 to 3 Sec)
220 VUp to 6 KVA6 KA  (1 to 3 Sec)


2. Substation Capacity and Short Circuit Current Capacity

As per Central Electricity Authority
Voltage Sub Station CapacityShort Circuit Current
765 KV4500 MVA31.5 KA for 1 Sec
400 KV1500 MVA31.5 KA for 1 Sec
220 KV500 MVA40 KA for 1 Sec
110/132 KV150 MVA40 KA or 50 KA for 1 Sec
66 KV75 MVA40 KA or 50 KA for 1 Sec


3. Minimum Ground Clearance and Fault Clearing Time

Voltage Min. Ground ClearanceFault Clear Time
400 KV8.8 Meter100 mille second
220 KV8.0 Meter120 mille second
132 KV6.1 Meter160 mille second
66 KV5.1 Meter300 mille second
33 KV3.7 Meter-
11 KV2.7 Meter-

4. Busbar Ampere Rating

For Phase BusbarAluminium 130 Amp / Sq.cm or 800Amp / Sq.inch.
For Phase BusbarCopper 160 Amp / Sq.cm or 1000Amp / Sq.inch
For Neutral BusbarSame as Phase Busbar up to 200 Amp than Size of Neutral Busbar is at least half of Phase Busbar.


5. Busbar Spacing

Between Phase and Earth26mm (Min)
Between Phase and Phase32mm (Min)
Busbar Support between Two Insulator250mm.


6. Sound Level of Diesel Generator (ANSI 89.2 and NEMA 51.20)

KVAMax. Sound Level
<9 kva="" td="">40 DB
10 KVA to 50 KVA45 DB
51 KVA to 150 KVA50 DB
151 KVA to 300 KVA55 DB
301 KVA to 500 KVA60 DB


7. IR Value of Transformer

IR Value of Transformer
Voltage30°C40°C50°C
>66KV600MΩ300MΩ150MΩ
22KV to 33KV500MΩ250MΩ125MΩ
6.6KV to 11KV400MΩ200MΩ100MΩ
<6 .6kv="" strong="">200MΩ100MΩ50MΩ
415V100MΩ50MΩ20MΩ

8. Standard Size of MCB, MCCB, ELCB, RCCB, SFU and Fuse

MCB, MCCB, ELCB, RCCB, SFU, Fuse – Standard Ratings
MCBUp to 63 Amp (80Amp and 100 Amp a    per Request)
MCCBUp to 1600 Amp (2000 Amp as per Request)
ACBAbove 1000 Amp
MCB Rating6A,10A,16A,20A,32A,40A,50A,63A
MCCB Rating0.5A,1A,2A,4A,6A,10A,16A,20A,32A,40A,50A,63A,80A,100A (Domestic Max 6A)
RCCB/ELCB6A,10A,16A,20A,32A,40A,50A,63A,80A,100A
Sen. of ELCB30ma (Domestic),100ma (Industrial),300ma
DPIC (Double Pole Iron Clad) main switch5A,15A,30 A for 250V
TPIC (Triple Pole Iron Clad) main switch30A, 60A, 100A, 200 A For 500 V
DPMCB5A, 10A, 16A, 32A and 63 A for 250V
TPMCCB100A,200A, 300Aand 500 A For 660 V
TPN main switch30A, 60A, 100A, 200A, 300 A For 500 V
TPNMCB16A, 32A,63A For 500 V, beyond this TPNMCCB: 100A, 200A, 300A, 500 A For 660 V
TPN Fuse Unit (Rewirable)16A,32A,63A,100A,200A
Change over switch (Off Load)32A,63A,100A,200A,300A,400A,630A,800A
SFU (Switch Fuse Unit)32A,63A,100A,125A,160A,200A,250A,315A,400A,630A
HRC Fuse TPN (Bakelite)125A,160A,200A,250A,400A.630A
HRC Fuse DPN (Bakelite)16A,32A,63A
MCB/MCCB/ELCB Termination Wire / Cable
Up to 20A MCBMax. 25 Sq.mm
20A to 63A MCBMax. 35 Sq.mm
MCCBMax. 25 Sq.mm
6A to 45A ELCB16 Sq.mm
24A to 63A ELCB35 Sq.mm
80A to 100A ELCB50 Sq.mm

Electrical Thumb Rule (Part 5)

Electrical Thumb Rules  (Part 5)

1. Standard Size of Transformer (IEEE/ANSI 57.120)

Single Phase TransformerThree Phase Transformer
5KVA, 10KVA, 15KVA, 25KVA, 37.5KVA, 50KVA, 75KVA, 100KVA, 167KVA, 250KVA, 333KVA, 500KVA, 833KVA, 1.25KVA, 1.66KVA, 2.5KVA, 3.33KVA, 5.0KVA, 6.6KVA, 8.3KVA, 10.0KVA, 12.5KVA, 16.6KVA, 20.8KVA, 25.0KVA, 33.33KVA3KVA, 5KVA, 9KVA, 15KVA, 30KVA, 45KVA, 75KVA, 112.5KVA, 150KVA, 225KVA, 300KVA, 500KVA, 750KVA, 1MVA, 1.5MVA, 2MVA, 2.5MVA, 3.7MVA, 5MVA, 7.5MVA, 10MVA, 12MVA, 15MVA, 20MVA, 25MVA, 30MVA, 37.5MVA, 50MVA, 60MVA, 75MVA, 100MVA


2. Standard Size of Motor (HP)

Electrical Motor (HP)
1, 1.5, 2, 3, 5, 7.5, 10, 15, 20, 30, 40, 50, 60, 75, 100, 125, 150, 200, 250, 300, 400, 450, 500, 600, 700, 800, 900, 1000, 1250, 1250, 1500, 1750, 2000, 2250, 3000, 3500 and 4000

3. Approximate RPM of Motor

HPRPM
< 10 HP750 RPM
10 HP to 30 HP>600 RPM
30 HP to 125 HP500 RPM
125 HP to 300 HP375 RPM

4. Motor Line Voltage

Motor (KW)Line Voltage
< 250 KW>440 V (LV)
150 KW to 3000KW2.5 KV to 4.1 KV (HV)
200 KW to 3000KW3.3 KV to 7.2 KV (HV)
1000 KW to 1500KW6.6 KV to 13.8 KV (HV)

5. Motor Starting Current

SupplySize of MotorMax. Starting Current
1 Phase< 1 HP6 X Motor Full Load Current
1 Phase1 HP to 10 HP3 X Motor Full Load Current
3 Phase10 HP2 X Motor Full Load Current
3 Phase10 HP to 15 HP2 X Motor Full Load Current
3 Phase> 15 HP1.5 X Motor Full Load Current


6. Motor Starter


StarterHP or KWStarting CurrentTorque
DOL<13 hp="" td="">7 X Full Load CurrentGood
Star-Delta13 HP to 48 HP3 X Full Load CurrentPoor
Auto TC> 48 HP (37 KW)4 X Full Load CurrentGood/ Average
VSD
0.5 to 1.5 X Full Load CurrentExcellent
Motor > 2.2KW Should not connect direct to supply voltage if it is in Delta winding


7. Impedance of Transformer (As per IS 2026)

>MVA% Impedance
< 1 MVA5%
1 MVA to 2.5 MVA6%
2.5 MVA to 5 MVA7%
5 MVA to 7 MVA8%
7 MVA to 12 MVA9%
12 MVA to 30 MVA10%
> 30 MVA12.5%


8. Standard Size of Transformer

Standard Size of TransformerKVA
Power Transformer (Urban)3, 6, 8, 10, 16
Power Transformer (Rural)1, 1.6, 3.15, 5
Distribution Transformer25, 50, 63, 100, 250, 315, 400, 500, 630