Electrical Thumb Rules (Part 6)
1. Transformer earthing wire / Strip size
| Size of T.C or DG | Body Earthing | Neutral Earthing |
| <315 kva="" strong="">315> | 25×3 mm Cu / 40×6 mm GI Strip | 25×3 mm Cu Strip |
| 315 KVA to 500 KVA | 25×3 mm Cu / 40×6 mm GI Strip | 25×3 mm Cu Strip |
| 500 KVA to 750 KVA | 25×3 mm Cu / 40×6 mm GI Strip | 40×3 mm Cu Strip |
| 750 KVA to 1000 KVA | 25×3 mm Cu / 40×6 mm GI Strip | 50×3 mm Cu Strip |
2. Motor earthing wire / Strip size
| Size of Motor | Body Earthing |
| < 5.5 KW | 85 SWG GI Wire |
| 5.5 KW to 22 KW | 25×6 mm GI Strip |
| 22 KW to 55 KW | 40×6 mm GI Strip |
| >55 KW | 50×6 mm GI Strip |
3. Panel earthing wire / Strip size
| Type of Panel | Body Earthing |
| Lighting & Local Panel | 25×6 mm GI Strip |
| Control & Relay Panel | 25×6 mm GI Strip |
| D.G & Exciter Panel | 50×6 mm GI Strip |
| D.G & T/C Neutral | 50×6 mm Cu Strip |
4. Electrical equipment earthing
| Equipment | Body Earthing |
| LA (5KA,9KA) | 25×3 mm Cu Strip |
| HT Switchgear | 50×6 mm GI Strip |
| Structure | 50×6 mm GI Strip |
| Cable Tray | 50×6 mm GI Strip |
| Fence / Rail Gate | 50×6 mm GI Strip |
5. Earthing wire (As per BS 7671)
| Cross Section Area of Phase, Neutral Conductor(S) mm2 | Minimum Cross Section area of Earthing Conductor (mm2) |
| S<=16 | S (Not less than 2.5 mm2) |
16 | 16 |
| S>35 | S/2 |
6. Area for transformer room: (As per NBC-2005)
| Transformer Size | Min. Transformer Room Area (M2) | Min. Total Sub Station Area( Incoming HV,LV Panel, T.C Roof) (M2) | Min. Space Width (Meter) |
| 1 x 160 | 14 | 90 | 9 |
| 2 x 160 | 28 | 118 | 13.5 |
| 1 x 250 | 15 | 91 | 9 |
| 2 x 250 | 30 | 121 | 13.5 |
| 1 x 400 | 16.5 | 93 | 9 |
| 2 x 400 | 33 | 125 | 13.5 |
| 3 x 400 | 49.5 | 167 | 18 |
| 2 x 500 | 36 | 130 | 14.5 |
| 3 x 500 | 54 | 172 | 19 |
| 2 x 630 | 36 | 132 | 14.5 |
| 3 x 630 | 54 | 176 | 19 |
| 2 x 800 | 39 | 135 | 14.5 |
| 3 x 800 | 58 | 181 | 14 |
| 2 x 1000 | 39 | 149 | 14.5 |
| 3 x 1000 | 58 | 197 | 19 |
- The capacitor bank should be automatically switched type for substation of 5MVA and higher.
- Transformer up to 25 KVA can be mounted direct on pole.
- Transformer from 25 KVA to 250KVA can be mounted either on
“H” frame of plinth.
- Transformer above 250 KVA can be mounted plinth only.
- Transformer above 100 MVA shall be protected by drop out fuse or circuit breaker.
7. Span of transmission line (Central electricity authority)
| Voltage | Normal Span |
| 765 KV | 400 to 450 Meter |
| 400 KV | 400 Meter |
| 220 KV | 335,350,375 Meter |
| 132 KV | 315,325,335 Meter |
| 66 KV | 240,250,275 Meter |
8. Max. lock rotor amp for 1-phase 230V motor (NEMA)
| HP | Amp |
| 1 HP | 45 Amp |
| 1.5 HP | 50 Amp |
| 2 HP | 65 Amp |
| 3 HP | 90 Amp |
| 5 HP | 135 Amp |
| 7.5 HP | 200 Amp |
| 10 HP | 260 Amp |
9. Three phase motor code (NEMA)
| HP | Code |
| <1 hp="" strong="">1> | L |
| 1.5 to 2.0 HP | L,M |
| 3 HP | K |
| 5 HP | J |
| 7 to 10 HP | H |
| >15 HP | G |
10. Service factor of motor
| HP | Synchronous Speed (RPM) |
| 3600 RPM | 1800 RPM | 1200 RPM | 900 RPM | 720 RPM | 600 RPM | 514 RPM |
| 1 HP | 1.25 | 1.15 | 1.15 | 1.15 | 1 | 1 | 1 |
| 1.5 to 1.25 HP | 1.15 | 1.15 | 1.15 | 1.15 | 1.15 | 1.15 | >1.15 |
| 150 HP | 1.15 | 1.15 | 1.15 | 1.15 | 1.15 | 1.15 | 1 |
| 200 HP | 1.15 | 1.15 | 1.15 | 1.15 | 1.15 | 1 | 1 |
| > 200 HP | 1 | 1.15 | 1 | 1 | 1 | 1 | 1 |
11. Type of contactor
| Type | Application |
| AC1 | Non Inductive Load or Slightly Inductive Load |
| AC2 | Slip Ring Motor, Starting, Switching OFF |
| AC3 | Squirrel Cage Motor |
| AC4,AC5,AC5a, AC5b,AC6a | Rapid Start & Rapid Stop |
| AC 5a | Auxiliary Control circuit |
| AC 5b | Electrical discharge Lamp |
| AC 6a | Electrical Incandescent Lamp |
| AC 6b | Transformer Switching |
| AC 7a | Switching of Capacitor Bank |
| AC 7b | Slightly Inductive Load in Household |
| AC 5a | Motor Load in Household |
| AC 8a | Hermetic refrigerant compressor motor with Manual Reset O/L Relay |
| AC 8b | Hermetic refrigerant compressor motor with Automatic Reset O/L Relay |
| AC 12 | Control of Resistive Load & Solid State Load |
| AC 13 | Control of Resistive Load & Solid State Load with Transformer Isolation |
| AC 14 | Control of small Electro Magnetic Load (<72 td="" va="">72> |
| AC 15 | Control of Electro Magnetic Load (>72 VA) |
12. Contactor coil
| Coil Voltage | Suffix |
| 24 Volt | T |
| 48 Volt | W |
| 110 to 127 Volt | A |
| 220 to 240 Volt | B |
| 277 Volt | H |
| 380 to 415 Volt | L |